Marginal note:Energy efficiency standards
130 (1) The energy efficiency standards set out in column 2 of the table to this section apply to single package vertical air conditioners described in column 1 that are manufactured during the periods set out in column 3.
Marginal note:Testing standard
(2) A single package vertical air conditioner complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by CSA C746-17 that are applicable to a single package vertical air conditioner as defined in section 128.
Item Column 1 Column 2 Column 3 Energy-using Product Energy Efficiency Standard Period of Manufacture 1 Single package vertical air conditioners that have a cooling capacity of < 19 kW (65,000 Btu/h) Energy efficiency ratio ≥ 9.0 On or after January 1, 2011 and before September 23, 2019 2 Single package vertical air conditioners that have a cooling capacity of < 19 kW (65,000 Btu/h) Energy efficiency ratio ≥ 11.0 On or after September 23, 2019 3 Single package vertical air conditioners that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 8.9 On or after January 1, 2011 and before October 9, 2015 4 Single package vertical air conditioners that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h) Energy efficiency ratio ≥ 10.0 On or after October 9, 2015 5 Single package vertical air conditioners that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) and < 70 kW (240,000 Btu/h) Energy efficiency ratio ≥ 8.6 On or after January 1, 2011 and before October 9, 2016 6 Single package vertical air conditioners that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h) and < 70 kW (240,000 Btu/h) Energy efficiency ratio ≥ 10.0 On or after October 9, 2016
- SOR/2019-163, s. 22
- Date modified: