Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Energy Efficiency Regulations, 2016

Version of section 130 from 2017-06-28 to 2019-12-11:


Marginal note:Energy efficiency standards

  •  (1) The energy efficiency standards set out in column 2 of the table to this section apply to single package vertical air conditioners described in column 1 that are manufactured on or after January 1, 2011.

  • Marginal note:Testing standard

    (2) A single package vertical air conditioner complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by CSA C746-06 that are applicable to a single package vertical air conditioner as defined in section 128.

    TABLE

    Column 1Column 2
    ItemEnergy-using ProductEnergy Efficiency Standard
    1Single package vertical air conditioners that have a cooling capacity of < 19 kW (65,000 Btu/h)Energy efficiency ratio ≥ 9.0
    2Single package vertical air conditioners that have a cooling capacity of ≥ 19 kW (65,000 Btu/h) and < 39.5 kW (135,000 Btu/h)Energy efficiency ratio ≥ 8.9
    3Single package vertical air conditioners that have a cooling capacity of ≥ 39.5 kW (135,000 Btu/h)Energy efficiency ratio ≥ 8.6

Date modified: