Government of Canada / Gouvernement du Canada
Symbol of the Government of Canada

Search

Chlorine Tank Car Unloading Facilities Regulations (C.R.C., c. 1147)

Regulations are current to 2024-08-18 and last amended on 2015-06-18. Previous Versions

SCHEDULE I(s. 19)

TABLE I

Minimum Clearance Distances Measured Horizontally Between the Track Side of a Chlorine Unloading Rack and the Gauge Side of the Nearest Rail of the Track Serving the Storage Facility

Minimum Distance from gauge side of nearest rail
STRAIGHT TRACK
  • (a) That portion of a rack or structure more than 4 feet above the top of the railblank line

6 feet
  • (b) Except as provided in (c), that portion of a rack or structure 4 feet or less above the top of the railblank line

3 feet 7¾ inchesFootnote for TABLE I Minimum Clearance Distances Measured Horizontally Between the Track Side of a Chlorine Unloading Rack and the Gauge Side of the Nearest Rail of the Track Serving the Storage Facility*
  • (c) Loading, unloading racks or terminals of an overall height of 4 feet or less above the top of the railblank line

6 feet
CURVED TRACK
All distances prescribed for straight track shall be increased by 1 inch per degree of track curvature
 

Date modified: