Energy Efficiency Regulations, 2016
Marginal note:Energy efficiency standards — single-phase
213 (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to single-phase split-system heat pumps described in column 1 that are manufactured during the periods set out in column 4.
Marginal note:Energy efficiency standards — three-phase
(1.1) The energy efficiency standards set out in column 3 of Table 2 to this section apply to three-phase split-system heat pumps described in column 1 that are manufactured during the periods set out in column 4.
Marginal note:Testing standard
(2) A split-system heat pump complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a split-system heat pump as defined in section 211.
Item Column 1 Column 2 Column 3 Column 4 Energy-using Product Standard Energy Efficiency Standard Period of Manufacture 1 Split-system heat pumps, other than those that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0
Heating seasonal performance factor (Region V) ≥ 6.7
On or after December 31, 1998 and before January 1, 2017 2 Split-system heat pumps, other than those that are small-duct and high-velocity CSA C656-14 for seasonal energy efficiency ratio and Heating seasonal performance factor
10 C.F.R. Appendix M for off mode power consumption
Seasonal energy efficiency ratio ≥ 14.0
Heating seasonal performance factor (Region V) ≥ 7.1
Off mode power consumption ≤ 33 W
On or after January 1, 2017 3 Split-system heat pumps that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 11.0
Heating seasonal performance factor (Region V) ≥ 5.9
On or after December 31, 1998 and before January 1, 2017 4 Split-system heat pumps that are small-duct and high-velocity CSA C656-14 for seasonal energy efficiency ratio and Heating seasonal performance factor
10 C.F.R. Appendix M for off mode power consumption
Seasonal energy efficiency ratio ≥ 12.0
Heating seasonal performance factor (Region V) ≥ 6.3
Off mode power consumption ≤ 30 W
On or after January 1, 2017 Column 1 Column 2 Column 3 Column 4 Item Energy-using Product Standard Energy Efficiency Standard Period of Manufacture 1 Split-system heat pumps, other than those that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0
Heating seasonal performance factor (Region V) ≥ 6.7
On or after December 31, 1998 and before January 1, 2017 2 Split-system heat pumps, other than those that are small-duct and high-velocity CSA C656-14 Seasonal energy efficiency ratio ≥ 14.0
Heating seasonal performance factor (Region V) ≥ 7.1
On or after January 1, 2017 3 Split-system heat pumps that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 11.0
Heating seasonal performance factor (Region V) ≥ 5.9
On or after December 31, 1998 and before January 1, 2017 4 Split-system heat pumps that are small-duct and high-velocity CSA C656-14 Seasonal energy efficiency ratio ≥ 12.0
Heating seasonal performance factor (Region V) ≥ 6.3
On or after January 1, 2017
- SOR/2019-163, s. 42
- Date modified: