Energy Efficiency Regulations, 2016
Marginal note:Energy efficiency standards
197 (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to large heat pumps described in column 1 that are manufactured during the periods set out in column 4 and that have no heating section or have an electric heating section.
Marginal note:Energy efficiency standards
(2) The energy efficiency standards set out in column 3 of Table 2 to this section apply to large heat pumps described in column 1 that are manufactured during the periods set out in column 4 and that have a heating section other than an electric heating section.
Marginal note:Testing standard
(3) A large heat pump complies with the energy efficiency standard set out in column 3 if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a large heat pump as defined in section 195.
Column 1 Column 2 Column 3 Column 4 Item Energy-using Product Testing Standard Energy Efficiency Standard Period of Manufacture 1 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-98 Energy efficiency ratio ≥ 10.1
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.2 with –8.3°C inlet air
On or after December 31, 1998 and before January 1, 2010 2 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 11.0
Heating coefficient of performance ≥ 3.3 with 8.3°C inlet air and ≥ 2.25 with –8.3°C inlet air
IEER ≥ 11.2
On or after January 1, 2010 and before January 1, 2018 3 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-17 Energy efficiency ratio ≥ 11.0
Heating coefficient of performance ≥ 3.3 with 8.3°C inlet air and ≥ 2.25 with –8.3°C inlet air
IEER ≥ 12.2
On or after January 1, 2018 4 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-98 Energy efficiency ratio ≥ 9.3
Heating coefficient of performance ≥ 3.1 with 8.3°C inlet air and ≥ 2.0 with –8.3°C inlet air
On or after December 31, 1998 and before January 1, 2010 5 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 10.6
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 10.7
On or after January 1, 2010 and before January 1, 2018 6 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-17 Energy efficiency ratio ≥ 10.6
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 11.6
On or after January 1, 2018 7 Large heat pumps that have a cooling capacity of ≥ 70 kW and < 223 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 9.5
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 9.6
On or after January 1, 2010 and before January 1, 2018 8 Large heat pumps that have a cooling capacity of ≥ 70 kW and < 223 kW CSA C746-17 Energy efficiency ratio ≥ 9.5
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 10.6
On or after January 1, 2018 Column 1 Column 2 Column 3 Column 4 Item Energy-using Product Testing Standard Energy Efficiency Standard Period of Manufacture 1 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-98 Energy efficiency ratio ≥ 9.9
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.2 with –8.3°C inlet air
On or after December 31, 1998 and before January 1, 2010 2 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 10.8
Heating coefficient of performance ≥ 3.3 with 8.3°C inlet air and ≥ 2.25 with –8.3°C inlet air
IEER ≥ 11.0
On or after January 1, 2010 and before January 1, 2018 3 Large heat pumps that have a cooling capacity of ≥ 19 kW and < 40 kW CSA C746-17 Energy efficiency ratio ≥ 10.8
Heating coefficient of performance ≥ 3.3 with 8.3°C inlet air and ≥ 2.25 with –8.3°C inlet air
IEER ≥ 12.0
On or after January 1, 2018 4 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-98 Energy efficiency ratio ≥ 9.1
Heating coefficient of performance ≥ 3.1 with 8.3°C inlet air and ≥ 2.0 with –8.3°C inlet air
On or after December 31, 1998 and before January 1, 2010 5 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 10.4
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 10.5
On or after January 1, 2010 and before January 1, 2018 6 Large heat pumps that have a cooling capacity of ≥ 40 kW and < 70 kW CSA C746-17 Energy efficiency ratio ≥ 10.4
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 11.4
On or after January 1, 2018 7 Large heat pumps that have a cooling capacity of ≥ 70 kW and < 223 kW CSA C746-06 for energy efficiency ratio and heating coefficient of performance
AHRI 340/360 for IEER
Energy efficiency ratio ≥ 9.3
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 9.4
On or after January 1, 2010 and before January 1, 2018 8 Large heat pumps that have a cooling capacity of ≥ 70 kW and < 223 kW CSA C746-17 Energy efficiency ratio ≥ 9.3
Heating coefficient of performance ≥ 3.2 with 8.3°C inlet air and ≥ 2.05 with –8.3°C inlet air
IEER ≥ 10.4
On or after January 1, 2018
- SOR/2018-201, s. 31
- SOR/2022-265, s. 47
- Date modified: