Energy Efficiency Regulations, 2016
Marginal note:Energy efficiency standards — single-phase
126 (1) The energy efficiency standards set out in column 3 of Table 1 to this section apply to single-phase single package central air conditioners described in column 1 that are manufactured during the periods set out in column 4.
Marginal note:Energy efficiency standards — three-phase
(1.1) The energy efficiency standards set out in column 3 of Table 2 to this section apply to three-phase single package central air conditioners described in column 1 that are manufactured during the periods set out in column 4.
Marginal note:Testing standard
(2) A single package central air conditioner complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by the standard set out in column 2 that are applicable to a single package central air conditioner as defined in section 124.
Item Column 1 Column 2 Column 3 Column 4 Energy-using Product Standard Energy Efficiency Standard Period of Manufacture 1 Single package central air conditioners, other than those that are through-the-wall or small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0 On or after February 3, 1995 and before January 1, 2017 2 Single package central air conditioners, other than those that are through-the-wall or small-duct and high-velocity CSA C656-14 for seasonal energy efficiency ratio
10 C.F.R. Appendix M for off mode power consumption
Seasonal energy efficiency ratio ≥ 14.0
Off mode power consumption ≤ 30 W
On or after January 1, 2017 3 Single package central air conditioners that are through-the-wall CSA C656-05 Seasonal energy efficiency ratio ≥ 10.6 On or after February 3, 1995 and before January 23, 2010 4 Single package central air conditioners that are through-the-wall CSA C656-05 Seasonal energy efficiency ratio ≥ 12.0 On or after January 23, 2010 and before January 1, 2017 5 Single package central air conditioners that are through-the-wall CSA C656-05 for seasonal energy efficiency ratio 10 C.F.R. Appendix M for off mode power consumption Seasonal energy efficiency ratio ≥ 12.0
Off mode power consumption ≤ 30 W
On or after January 1, 2017 6 Single package central air conditioners that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0 On or after February 3, 1995 and before January 1, 2017 7 Single package central air conditioners that are small-duct and high-velocity CSA C656-14 for seasonal energy efficiency ratio
10 C.F.R. Appendix M for off mode power consumption
Seaonal energy efficiency ratio ≥ 12.0
Off mode power consumption ≤ 30 W
On or after January 1, 2017 Column 1 Column 2 Column 3 Column 4 Item Energy-using Product Standard Energy Efficiency Standard Period of Manufacture 1 Single package central air conditioners, other than those that are through-the-wall or small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0 On or after February 3, 1995 and before January 1, 2017 2 Single package central air conditioners, other than those that are through-the-wall or small-duct and high-velocity CSA C656-14 Seasonal energy efficiency ratio ≥ 14.0 On or after January 1, 2017 3 Single package central air conditioners that are through-the-wall CSA C656-05 Seasonal energy efficiency ratio ≥ 10.6 On or after February 3, 1995 and before January 23, 2010 4 Single package central air conditioners that are through-the-wall CSA C656-05 Seasonal energy efficiency ratio ≥ 12.0 On or after January 23, 2010 5 Single package central air conditioners that are small-duct and high-velocity CSA C656-05 Seasonal energy efficiency ratio ≥ 13.0 On or after February 3, 1995 and before January 1, 2017 6 Single package central air conditioners that are small-duct and high-velocity CSA C656-14 Seasonal energy efficiency ratio ≥ 12.0 On or after January 1, 2017
- SOR/2019-163, s. 19
- Date modified: