Maritime Occupational Health and Safety Regulations

Version of section 157 from 2010-06-03 to 2023-12-19:

  •  (1) The average level of lighting at a task position set out in column 1 of the table to this subsection must not be more than the average level set out in column 2.

    TABLE

    Average Levels of Lighting — VDT Work

    Column 1Column 2
    ItemTask PositionAverage Level in lx
    1VDT Work
    • (a) Task positions at which data entry and retrieval work are performed intermittently

    500
    • (b) Task positions at which data entry work is performed exclusively

    750
  • (2) Reflection glare on a VDT screen must be reduced to the point where an employee at a task position is able to read every portion of any text displayed on the screen and see every portion of the visual display on the screen.

  • (3) If VDT work requires the reading of a document, supplementary lighting must be provided where necessary to give a level of lighting of at least 500 lx on the document.