Hull Construction Regulations
235 (1) Subject to subsection (2), no duct provided for the ventilation of a machinery space of Category ‘A’, galley or car deck space shall pass through an accommodation space, service space or control station unless the duct is
(a) constructed of steel that,
(i) in the case of a duct that has a diameter or width of 300 mm or less, has a thickness of at least 3 mm,
(ii) in the case of a duct that has a diameter or width greater than 760 mm, has a thickness of at least 5 mm, or
(iii) in the case of a duct that has a diameter or width greater than 300 mm but not greater than 760 mm, has a thickness determined by interpolation;
(b) suitably supported and stiffened; and
(c) insulated to an ‘A-60’ Class fire rating throughout the accommodation space, service space or control station.
(2) A duct provided for the ventilation of a machinery space of Category A, galley or car deck space may pass through an accommodation space, service space or control station if the duct is
(a) constructed of steel;
(b) fitted close to every boundary penetrated with a fire damper that is
(i) of the fail-safe automatic closing type, and
(ii) capable of being manually operated from either side of the division; and
(c) insulated to an ‘A-60’ Class fire rating from the machinery space, galley or car deck space to a point at least 5 m beyond each fire damper.
- SOR/83-521, s. 4